REF16-S124-DC24V-6A ETA Electronic circuit breaker
Selective load protection
Electronic switch-off characteristic
Control input IN+
Status output SF
- Buy 10 for €51.72 each and save 5%
- Buy 25 for €47.48 each and save 13%
- Buy 50 for €43.66 each and save 20%
- Buy 100 for €42.39 each and save 22%
The REF16-S device expands the "electronic overcurrent protection" product group for DC 24 V applications.
It selectively protects all DC 24 V load circuits with a width of just 12.5 mm. This is achieved by a combination of active electronic current limitation in the event of a short circuit and an overload cut-out at typ. 1.25 x IN. In combination with the E-T-A plug-in bases 80plus and 81plus, the REF16-S
can be installed quickly, conveniently and flexibly. The bases enable power distribution and signal distribution via pluggable bridges.
The REF16-S is also latched to the base and can be assigned to fixed current levels or slots using a coding pin. The installation dimensions comply with the DIN 43880 standard for installation devices.
DC 24 V switched-mode power supply units are frequently used in automation technology. However, in the event of an overload, they reduce the output voltage that is intended to supply all connected loads. If a fault occurs in a single load in the system, the voltage in all other load circuits also drops. This often results not only in an undefined fault condition, but also in the machine or system coming to a standstill.
This is precisely where the REF16-S comes into play by reacting to the overload condition faster than the switching power supply. The maximum possible overcurrent is always limited to typically 1.25 times the selected rated current (see Table 1). This means that capacitive loads up to 20,000 μF can be switched on, but are switched off in the event of an overload or short circuit. To adapt to the load conditions, the rated current is available in fixed values of 0.5 A...10 A. Operating and error states are indicated by a multi-coloured LED, a potential-free signal contact or by an integrated short-circuit-proof status output. Remote operation is possible via a remote reset signal or a remote ON/OFF control signal. The manual ON/OFF switch directly on the device allows targeted commissioning of individual load circuits.
As soon as the REF16-S detects an overload or short circuit in its load circuit, it blocks the load output transistor and thus interrupts the current flow in the faulty circuit. Once the fault has been rectified, the load output of the REF16-S is reactivated by an electronic reset signal or manually by pressing the ON/OFF switch directly on the device.
Key features:l Pluggable in socket 80plus and socket 81plus
- Active linear current limitation
l Capacitive loads up to 20,000µF
l Rated current in fixed current ratings 0.09 A...10 A
l Device plus socket comply with the installation dimensions according to DIN 43880
l Approvals: UL, CSA, GL
l Meets requirements according to NEC Class 2
l OPTION: control inputs, signalling
Technical details:
operating voltage UB | dC 24 V (18...30 V) |
connection | lINE+ (1) GND (12(b)) |
rated current IN | fixed currents: 0.5 A, 1 A, 2 A, 3 A, 4 A, 6 A, 8 A, 10 A |
quiescent current I0 |
in ON state: typ. 8 mA |
signalling of the operating status via |
- device switched on Load circuit controlled Orange: - overload until switch-off Red: - after an overload/short circuit switch-off - short circuit until switch-off - in case of undervoltage in single state - device switched off via the control input IN+ OFF: - Device switched off via the ON/OFF switch - Missing operating voltage
|
load circuit | |
load output | power - MOSFET switching output (plus switching) |
connection | lOAD+ (2) |
overload and short-circuit current cut-off | typ. 1.25 x IN with active current limitation |
switch-off times | see time / current characteristic typ. 80 - 800 ms depending on rated current |
temperature switch-off | internal temperature monitoring with electronic switch-off |
operating voltage monitoring for undervoltage |
oFF: at typ. UB < 14 V ON: at typ. UB > 17 V with automatic OFF and ON switching |
switch-on delay tStart | typ. 2 ms after each switch-on, after reset and after the application of UB |
switching off the load circuit | electronic switch-off without galvanic isolation |
leakage current in the load circuit in the OFF state | typ. 1 mA |
capacitive loads | up to 20 000 µF |
freewheeling circuit | external freewheeling diode recommended for inductive loads |
parallel connection of several load outputs | not permitted |
Approvals:
Test centre |
Test standard | File Certificate No. |
Rated voltage | Rated current range |
UL | UL 2367 | E306740 | DC 24 V | 0.5 A...10 A |
UL *) | UL 508 CSA C22.2 No. 14 |
E322549 | DC 24 V | 0.5 A...10 A |
CSA *) | CSA C22.2 No.213 (Class I, Division 2, Groups A, B, C, D) |
165971 | DC 24 V | 0.5 A...10 A |
DNV GL |
CG-0339 (classes: temperature, EMC: B; humidity, vibration: A) |
TAE000039W | DC 24 V | 0.5 A...10 A |
*) cULus (listed) and CSA when used
with socket 80plus or socket 81plus
Item name | REF16-S124-DC24V-6A ETA Electronic circuit breaker |
---|---|
SKU | 24-02003 |
Weight | 0.028000 |
Version | 1 ohne galvanische Trennung |
Design: Communication, interface | 01 analog Signal |
Country of manufacture | Germany |
Signal output | 7 Status output |
Connection type Main connections | P10 flat plug DIN 46244-A6.3-0.8 |
Series | REF16 |
Signal input | 2 with reset input RE |
Actuating element | W Standard rocker switch |
Undervoltage module | none |
Operating voltage | DC 24 V |
Number of poles | 1-pole thermally protected |
Rated current range | 6A |
Mounting type | S Pluggable |
Characteristic | Medium time-lag tripping characteristic (standard) |
Additional function | 0 ohne |
Traub order number | REF16-S124-DC24V-6A |
Commodity code | 85362010 |
Manufacturer | E-T-A |