ESS22-TA-001-DC24V-2A ETA Electronic circuit breaker
Electronic circuit breaker
Mounting rail mounting with ON/OFF slide actuation
Operating voltage DC 24 V
Rated voltage 2A
- Buy 10 for €147.55 each and save 5%
- Buy 25 for €135.46 each and save 12%
- Buy 50 for €124.57 each and save 20%
- Buy 100 for €120.94 each and save 22%
The device ESS22-T extends the product group "Electronic circuit breakers" for DC 24 V applications. It is a two-pole version with galvanic isolation. The ESS22-T thus complies with the requirements of the Machinery Directive 2006/42/EC and the associated standard EN 60204-1 "Safety of machinery, electrical equipment of machines", par. 9.4.3.1
The combination of active electronic current limitation in the event of a short circuit and an overload cut-off from 1.1 x IN selectively and bipolarly protects the DC 24 V load circuits. The ESS22-T can be snapped directly onto the top-hat rail and thus offers fast and flexible mounting for groups of devices with several DC 24 V circuits fed by switched-mode power supplies or transformer power supplies.
DC 24 V switched-mode power supplies are used very frequently in automation technology. However, in the event of an overload, they regulate the output voltage that is to supply all connected loads. So if a fault occurs in a single load in the system, the voltage also collapses in all other load circuits. Often, this results not only in an undefined fault condition, but even in a standstill of the machine or system.
This is exactly where the ESS22-T intervenes by reacting faster than the switched-mode power supply to the overload condition. The maximum possible overcurrent is always limited to typically 1.4 times the selected rated current. This allows capacitive loads up to 20,000 μF to be switched on, but they are only switched off in the event of an overload or short circuit. For adaptation to the load conditions, the nominal current is available in fixed values of 0.5 A...10 A. Operating and error states are indicated by a visual display and via signal contacts. Remote operation is optionally possible via an electrically isolated control input.
The manual ON/OFF switch directly on the unit allows targeted commissioning of individual load circuits. As soon as the ESS22-T detects an overload or short circuit in its load circuit, it blocks the load output transistor and thus interrupts the current flow in the faulty circuit; in addition, the load output is galvanically isolated by a mechanical switching element with two poles. After the fault has been rectified, the load output of the ESS22-T is reactivated manually by actuating the ON/OFF switch directly on the unit or optionally by the galvanically isolated reset input or by the control input.
Key features:
- Two-pole electronic circuit breaker with galvanic isolation at the load output
- "LOAD+ path" 2-fold protected with electronic fuse and fail-safe element
- "LOAD- path" 2-fold protected with electronic fuse protection and fail-safe element
- Selective load fuse protection, electronic switch-off characteristic curve
- Active current limitation when switching on capacitive loads up to 20,000 μF, DC motors and in case of overload/short circuit
- Rated current selectable in fixed amperages 0.5 A...10 A
- Operating voltage monitoring for undervoltage
- Manual on/off switch (ON/OFF) on the unit
- Option: Galvanically isolated control input for ON/OFF
- Option: Galvanically isolated reset input RE
- Optical signalling by multi-coloured LED
- 2 signal contacts (NC and NO) Construction width 22.5 mm
- For direct top-hat rail mounting
Technical data:
operating data | |
operating voltage UB | dC 24 V (18...32 V) |
rated current IN | fixed currents: 0.5 A, 1 A, 2 A, 3 A, 4 A, 6 A, 8 A, 10 A |
quiescent current I0 | in ON state: typ. 27 mA with signal output: typ. 37 mA |
signalling of operating status via |
|
load circuit | |
load output | power - MOSFET and relay Switching output with galvanic isolation, plus and minus switching |
overload cut-off (ÜL) | typ. 1.1 x IN (1.05...1.35 x IN) |
short-circuit current IK | active current limitation typ. 1.4 x IN (see Table 1) |
switch-off times | see time/current characteristic typ. 3 s at Iload > 1.1 x IN typ. 100 ms...3 s at Iload > 1.4 x IN |
temperature shut-off |
internal temperature monitoring with |
operating voltage monitoring for undervoltage |
oFF at typ. UB < 16.0 V ON at typ. UB > 17.5 V with automatic OFF and ON switching |
switch-on delay tStart | typ. 0.5 s after each switch-on, after reset and after application of UB |
switching off the load circuit | is two-pole with galvanic isolation - manually on the unit with the ON/OFF switch (OFF) - after an overload/short-circuit switch-off - via external control input - in case of undervoltage - in case of no operating voltage |
resetting (RESET) or switching on again after an overload/short-circuit shutdown |
- First rectify the external overload or short-circuit fault - Manual RESET on the unit via switch: OFF/ON - No reset during power interruptions (the state is saved) - No reset possible via the external control input IN - External reset optionally possible via the reset input RE |
free-wheeling circuit | external freewheeling diode recommended for inductive load |
parallel connection of several load outputs | not permissible |
signal output ESS22-TA-0x1 | |
electrical data | potential-free signal contact 1 NC contact, terminal 11-12 (closed in off or fault state) 1 NO contact, terminal 13-14 (open in off or fault state) max. DC 30 V/0.5 A, min. 10 V/10 mA |
error pattern | signal output is in fault condition: - Manually at the unit with the ON/OFF switch (OFF) - After an overload/short circuit Switch-off - External control input (OFF) - Undervoltage - In the absence of operating voltage |
control input IN+ / IN- ESS22-TA-01x / ESS22-TA-03x | |
electrical data | control input (IN+/IN-) is galvanically isolated from the load circuit (optocoupler) Voltage max. + DC 32 V High > DC 12 V ≤ DC 32 V (switch-on) Low ≤ DC 5 V > 0 V (switch-off) Current consumption typ. 3...9 mA (DC +12 V...32 V) |
reset function | eSS22-TA-03x A blocked load output (blocked after an overload/short-circuit (switch-off) can be switched on again by the control input external . For this, the control input must be switched off for at least >100 ms. |
links | manual ON/OFF switch on the unit is linked to the external control input IN+ with an AND function. |
reset input RE+ / RE- ESS22-TA-02x | |
Electrical data | reset input (RE+/RE-) is electrically isolated from the load circuit (optocoupler) Voltage max. + DC 32 V High > DC 12 V ≤ DC 32 V Low ≤ DC 5 V > 0 V Current consumption typ. 3...9 mA (DC +12 V...32 V) RESET - pulse/edge from low (min. 100 ms) to high (min. 100 ms) |
reset signal RE | a blocked load output (blocked after an overload/short-circuit disconnection) can be switched on again by an external reset pulse (+ DC 24 V). a common reset signal can also be applied simultaneously to several ESS22-T units ; units that are switched on remain unaffected. |
general data | |
fail-safe element | integrated fail-safe element adapted to the rated current (fuse element) |
connection terminals | |
screw terminals Connection capacity (conductor cross-section) rigid/flexible Stripping length Tightening torque (EN 60934) Loop-through possibility |
m3 0.14 - 2.5 mm2 (AWG 26-14) 8 mm 0.5 - 0.6 Nm Connections LINE+ and LINE are double. maximum continuous load for supply 10 A |
enclosure material | plastic |
enclosure mounting | top-hat rail according to EN 50022-35x7.5 |
ambient temperature | 0...50 °C (without condensation, see EN 60204-1) |
storage temperature | -20...70 °C |
humidity heat | 96 hrs./95 % relat. Humidity/40 °C according to IEC 60068-2-78, Test Cab. Climate class 3K3 according to EN 60721 |
vibration resistance | 3 g, test acc. to IEC 60068-2-6, test Fc |
protection class | enclosure IP20 DIN 40050 Terminals IP20 DIN 40050 |
standards, regulations | cE mark according to EMC directive Emitted interference: EN 61000-6-3 Interference immunity: EN 61000-6-2 Surge voltages: EN 61000-4-5 (± 1 kV symmetrical) |
insulation coordination 0.5 kV/pollution degree 2 (IEC 60934) |
0.5 kV/pollution degree 2 |
insulation voltage | dC 500 V Between the galvanically isolated areas: load circuit in off-state, signal input and signal outputs |
dielectric strength | max. DC 32 V |
reverse polarity protection | reverse polarity protection |
installation dimensions (W x H x D) | see dimensional drawing (tolerances according to DIN ISO 268 part 1 ± IT 13) |
weight | approx. 110 g |
Approvals:
test centre | rated voltage | rated current range |
vDE (EN 60934) | dC 24 V | 0,5...10 A |
uL 1077 in preparation | dC 24 V | 0,5...10 A |
Item name | ESS22-TA-001-DC24V-2A ETA Electronic circuit breaker |
---|---|
SKU | 24-01276 |
Weight | 0.102800 |
Version | 0 mit zweipoliger galvanischer Trennung am Lastausgang |
Design: Communication, interface | 01 analog Signal |
Country of manufacture | Germany |
Signal output | 1 with signal contacts: 1 NC contact, 1 NO contact |
Connection type Main connections | P10 flat plug DIN 46244-A6.3-0.8 |
Series | ESS22-T |
Signal input | 0 without signal input |
Actuating element | W Standard rocker switch |
Undervoltage module | none |
Operating voltage | DC 24 V |
Number of poles | 1-pole thermally protected |
Rated current range | 2A |
Mounting type | TA mounting rail attachment, without signal contact |
Characteristic | Medium time-lag tripping characteristic (standard) |
Additional function | 0 ohne |
Traub order number | ESS22-TA-001-DC24V-2A |
Commodity code | 85362010 |
Manufacturer | E-T-A |
Manufacturer number | ESS22-TA-001-DC24V-2A |