ESX10-125-DC24V-4A ETA Electronic circuit breaker
E-T-A Electronic circuit breaker with current limiting
Manual on/off switch
Construction width per channel only 12.5 mm
Rated voltage DC 24 V
Rated current 4 A
- Buy 10 for €61.62 each and save 5%
- Buy 25 for €56.57 each and save 12%
- Buy 50 for €52.03 each and save 20%
- Buy 100 for €50.50 each and save 22%
Artikel dem Warenkorb hinzufügen oder Alles auswählen
The ESX10 unit expands the "electronic overcurrent protection" product group for DC 24 V applications. With a width of only 12.5 mm, it selectively protects all DC 24 V load circuits. This is achieved by a combination of active electronic current limitation in the event of a short circuit and an overload cut-off from 1.1 x IN. In combination with the E-T-A power distributors Modul 17plus and SVSxx, the ESX10 offers fast, convenient and flexible installation. DC 24 V switched-mode power supplies are used very frequently in automation technology. However, in the event of an overload, they regulate the output voltage that is to supply all connected loads. So if a fault occurs in a single load in the system, the voltage also collapses in all other load circuits. Often, this results not only in an undefined fault condition, but even in a standstill of the machine or system. This is exactly where the ESX10 intervenes by reacting faster than the switching power supply to the overload condition. The maximum possible overcurrent is always limited to 1.3...1.8 times the selected rated current (see Table 1). This makes it possible to switch on capacitive loads up to 75,000 µF, but they are only switched off in the event of an overload or short circuit. For adaptation to the load conditions, the nominal current is available in fixed values of 0.5 A...12 A. Operating and fault states are indicated by a multi-coloured LED, an integrated short-circuit-proof status output or individual or group alarms. Remote operation is possible via a remote reset signal or a remote ON/OFF control signal. The manual ON/OFF switch directly on the unit allows targeted commissioning of individual load circuits. As soon as the ESX10 detects an overload or short circuit in its load circuit, it disables the load output transistor and thus interrupts the current flow in the faulty circuit. Once the fault has been rectified, the load output of the ESX10 is reactivated by an electronic reset signal or manually by pressing the ON/OFF switch directly on the unit.
Main features:
- Selective load protection, electronic shutdown characteristic l Active current limitation when switching on capacitive loads up to 75,000 µF and in the event of overload/short circuit
- Rated current selectable in fixed amperages 0.5 A...12 A
- Safe overload cut-off from 1.1 x IN even with long load lines or low line cross-sections (see Table 3)
- Manual ON/OFF switch (S1) l Control input IN+ for remote ON/OFF signal (option)
- Clear signalling by LED, status output SF or signal contact F (can be combined) l Electronic reset input RE (option)
- Integrated fail-safe element
- Width per channel only 12.5 mm
- Can be plugged into bayable power distribution module 17plus, optionally onto power distribution SVS02/SVS04 (see product group Power Distribution Systems)
- Additional versions with ATEX approval available Marking:
Technical data:
operating data | |
operating voltage UB | dC 24 V (18...32 V) |
rated currentIN | fixed currents: 0.5 A, 1 A, 2 A, 3 A, 4 A, 6 A, 8 A, 10 A, 12 A |
quiescent current I0 | in ON state: typ. 20...30 mA depending on signal output |
signalling of the operating state via |
multicolour LED: |
load circuit | |
load output | power MOSFET switching output (positive switching) |
overload cut-off (ÜL) | typ. 1.1 x IN (1.05...1.35 x IN) |
short-circuit current IK | active current limitation (see Table 1) |
switch-off times see time/current characteristic for electronic switch-off Switch-off |
see time/current characteristic for electronic switch-off. Switch-off: typ. 3 s forIload > 1.1 xIN typ. 100 ms...3 s forIload > 1.8 xIN (or 1.5 xIN/1.3 xIN, ) |
temperature shut-off | internal temperature monitoring with electronic switch-off |
undervoltage monitoring of the load output | with hysteresis, no reset necessary: load "OFF" at UB < 8 V |
switch-on delay tStart | typ. 0.5 s after each switch-on, after reset and after application of UB |
switch-off of the load circuit | electronic switch-off after overload/short circuit |
free-wheeling circuit | external free-wheeling diode recommended for inductive load |
parallel connection of several load outputs | not permissible |
Approvals:
test standard | rated voltage | rated current range |
uL 2367 | dC 24 V | 0,5...12 A |
uL 1604 | dC 24 V | 0,5...12 A |
uL 508 CSA C22.2 No. 14 |
dC 24 V | 0,5...12 A |
c22.2 No. 142 C22.2 No. 213 (class I, division 2) |
dC 24 V | 0,5...12 A |
aTEX 94/9/EC |
dC 24 V | |
rules VI, part 7, GL 2012, category C, EMC1 | iI 3G Ex nA IIB T4 Gc X | iI 3G Ex nA IIB T4 Gc X |
Item name | ESX10-125-DC24V-4A ETA Electronic circuit breaker |
---|---|
SKU | 24-00745 |
Weight | 0.054600 |
Version | 1 ohne galvanische Trennung im Fehlerfall |
Design: Communication, interface | 01 analog Signal |
Country of manufacture | Germany |
Signal output | 5 Signalling output F (NO contact/ ESX10-115 and ESX10-125 only) |
Connection type Main connections | P10 flat plug DIN 46244-A6.3-0.8 |
Series | ESX10 |
Signal input | 2 with reset input RE |
Actuating element | W Standard rocker switch |
Undervoltage module | none |
Operating voltage | DC 24 V Nennspannung DC 24 V |
Number of poles | 1-pole thermally protected |
Rated current range | 4A |
Mounting type | S Pluggable |
Characteristic | Medium time-lag tripping characteristic (standard) |
Additional function | 0 ohne |
Traub order number | ESX10-125-DC24V-4A |
Commodity code | 85362010 |
Manufacturer | E-T-A |